Rex Drive Isolation Transformers |
HH Roberts recommends the use of these K-Factor rated transformers to power CNC machines to do two things for the installation: 1) clean up an unbalanced or wild leg power supply to give balanced voltage on all three legs ( measured leg to ground, not leg to leg ) 2) avoid feedback of harmonics to the power in the building that could cause interference on other sensitive equipment. These harmonics are generated within the variable speed drives used by CNC machines. To be effective these transformers must be connected with the X0 tap grounded. |
The following is copied from the Rex web site.
Overview of K-Factor Rated Transformers Today's modern electronic, electric components and circuitry such as computers, copiers, printers, fax machines and display terminals utilize switching mode power supplies for their operation. These switching mode power supplies are non-linear in nature and can cause significant power system problems:
A linear load uses current from the power source continuously over the sinusoidal cycle. A non-linear load uses current in large pulses from the power source thereby creating harmonic distortion. Harmonic components are represented by periodic waves that have a frequency that is a multiple of the fundamental frequency. Example:
Effects of Harmonic Components on the Sinusoidal Cycle ![]() K-Factor Ratings A K-Factor Rating applied to a transformer is an index of the transformers ability to supply harmonic content in its load current while operating within its temperature limits. For Dry Type Transformers a K-Factor calculation is made to determine the amount of the Harmonic Content present in a power system. K-Rated Transformers are sized to handle 100% of the fundamental 60Hz load, plus the non-linear load specified. The neutral of the K-Rated transformer is sized at 200% of the current rating of the phase connections. K-Factor 1: Motors, Incandescent Lighting, Resistance Heating, Motor Generators (without solid state drives) K-Factor 4: HID Lighting, Induction Heaters, Welders, UPS with optional input filtering, PLC and solid state controls K-Factor 13: Multiple receptacle circuits in health care facilities, UPS without optional input filtering, Production or assemble line equipment, Schools and Classroom facilities K-Factor 20: SCR Variable Speed Drives, Circuits with exclusive data processing equipment, Critical care facilities and Hospital operating rooms What about other K-Factor Ratings? We can calculate K-Factor Ratings or any magnitude when Harmonic Values are given Application Our Drive Isolation Transformers (DIT) are specifically designed to meet the requirements of AC or DC Variable Speed Drives or Rectifier outputs and are rated to match standard motor HP voltage ratings. Features
Common Part Numbers & Typical Information Some enclosure dimensions may have changed. Click here for more info Available Options Include
|
Drive Rating | Recommended Transformer Size (DIT) |
Aluminum Windings 575 ![]() 460Y/266 |
Aluminum Windings 460 ![]() 460Y/266 |
Aluminum Windings 460 ![]() 230Y/133 |
Aluminum Windings 230 ![]() 230Y/133 |
Indoor Enclosure Size |
Typical Weight |
5HP | 8KVA | DA8J1P1 | DA8H1P1 | DA8H1S1 | DA8C1S1 | #4 | 135LBS |
8HP | 11KVA | DA11J1P1 | DA11H1P1 | DA11H1S1 | DA11C1S1 | #4 | 150LBS |
10HP | 14KVA | DA14J1P1 | DA14H1P1 | DA14H1S1 | DA14C1S1 | #5 | 182LBS |
15HP | 20KVA | DA20J1P1 | DA20H1P1 | DA20H1S1 | DA20C1S1 | #6 | 247LBS |
20HP | 27KVA | DA27J1P1 | DA27H1P1 | DA27H1S1 | DA27C1S1 | #6 | 275LBS |
25HP | 34KVA | DA34J1P1 | DA34H1P1 | DA34H1S1 | DA34C1S1 | #6 | 310LBS |
30HP | 40KVA | DA40J1P1 | DA40H1P1 | DA40H1S1 | DA40C1S1 | #6 | 336LBS |
40HP | 51KVA | DA51J1P1 | DA51H1P1 | DA51H1S1 | DA51C1S1 | #7 | 455LBS |
50HP | 63KVA | DA63J1P1 | DA63H1P1 | DA63H1S1 | DA63C1S1 | #7 | 485LBS |
60HP | 75KVA | DA75J1P1 | DA75H1P1 | DA75H1S1 | DA75C1S1 | #7 | 565LBS |
75HP | 93KVA | DA93J1P1 | DA93H1P1 | DA93H1S1 | DA93C1S1 | #8 | 755LBS |
100HP | 118KVA | DA118J1P1 | DA118H1P1 | DA118H1S1 | DA118C1S1 | #8 | 820LBS |
125HP | 145KVA | DA145J1P1 | DA145H1P1 | DA145H1S1 | DA145C1S1 | #8 | 890LBS |
150HP | 175KVA | DA175J1P1 | DA175H1P1 | DA175H1S1 | DA175C1S1 | #9 | 1250LBS |
200HP | 220KVA | DA220J1P1 | DA220H1P1 | DA220H1S1 | DA220C1S1 | #9 | 1470LBS |
250HP | 275KVA | DA275J1P1 | DA275H1P1 | DA275H1S1 | DA275C1S1 | #9 | 1750LBS |
300HP | 330KVA | DA330J1P1 | DA330H1P1 | DA330H1S1 | DA330C1S1 | #9 | 1990LBS |
400HP | 440KVA | DA440J1P1 | DA440H1P1 | DA440H1S1 | DA440C1S1 | #10 | 2700LBS |
500HP | 550KVA | DA550J1P1 | DA550H1P1 | DA550H1S1 | DA550C1S1 | #40 | 3100LBS |